Laserfiche WebLink
<br /> <br />P23-0480 and TR8680 Planning Commission April 23, 2025 <br />Page 24 of 31 <br />of a building having a fire alarm system, the Fire Department shall test and witness the <br />operation of the fire alarm system. <br /> <br />106. ELECTRICAL CONDUIT: Electrical conduit shall be provided to each fire protection <br />system control valve, including all valve(s) at the water connections. The Livermore- <br />Pleasanton Fire Department requires electronic supervision of all valves for automatic <br />sprinkler systems and fire protection systems. <br /> <br />107. LISTED: All commercial, industrial, and multi-family residential occupancies shall have <br />valve tamper and water flow connected to a listed Central Station Service in accordance <br />with NFPA 72. Fire Department plan check includes specifications, monitoring, <br />installation, and alarm company certificates. Fire alarm control panel and remote <br />annunciation shall be at location(s) approved by the Fire Prevention Bureau. All systems <br />shall be point identified by individual device and annunciated by device type and point. <br /> <br />108. HAZARDOUS MATERIALS DECLARATION: A Hazardous Materials Declaration shall be <br />provided for this tenant and/or use. The form shall be signed by the owner/manager of <br />company occupying the suite/space/building. No building permit shall be issued until the <br />Hazardous Materials Declaration is provided. The form is available from the Livermore- <br />Pleasanton Fire Department, Fire Prevention Bureau. <br /> <br />109. HAZARDOUS MATERIALS: Should any operation or business activity involve the use, <br />storage or handling of hazardous materials, the firm shall be responsible for contacting <br />the Livermore-Pleasanton Fire Department prior to commencing operations. Please <br />contact the Hazardous Materials Coordinator at 925/454-2361. <br /> <br />110. FIRE HYDRANTS: Fire hydrants shall be installed at spacing not greater than 300 feet in <br />industrial and commercial developments. Fire hydrants shall be installed at spacing not <br />greater than 400 feet in residential developments. <br /> <br />111. FIRE LANE MARKING: On-site access ways, turn arounds, and internal drives shall be <br />designated as fire lanes and identified as such by red curb striping and posted with signs <br />at locations approve by the Fire Department. Signs shall be according to State sta ndards <br />and read “No Parking – Fire Lane” and must be shown on the Project Plans. The red curb <br />striping, sign location(s), and sign language shall be included in the building permit <br />submittal for review and approval by the Livermore-Pleasanton Fire Department prior to <br />building permit issuance. <br /> <br />a. The following schedule for NO PARKING signs shall apply: <br /> <br />Width Requirements <br />36 feet or greater No requirements <br />Between 28 and 36 feet Post one side <br />Between 20 and 28 feet Post both sides <br />Less than 20 feet Not permitted <br />Cul-de-Sac Not permitted <br /> <br />Docusign Envelope ID: 2B93F64A-C49E-4C2A-BF54-785F6FDA6546