Laserfiche WebLink
Exception #2: Sprinklers may be omitted from small closets where the least dimension <br />does not exceed 3 feet. (0.9 M), the area does not exceed 24 square feet (2.2 m), and <br />the walls and ceiling are surfaced with non-combustible materials. <br />Exception #3: Sprinklers may be omitted from attics and crawl spaces which are not <br />used or intended for living purposes or storage in buildings with no more than four (4) <br />dwelling units, except pilot sprinklers are required as per section 4-2.6 (above). <br />Note: See Chapter 4 System Design for provisions in buildings with five (5) to fifteen <br />(15) dwelling units not exceeding twelve thousand square feet (12,000 square feet). <br />CHAPTER 4-System Design -amended <br />Table 4-4.3(a) Pressure Losses in psi/ft. for Schedule 40 Steel Pipe(C=120) and Table <br />4-4.3(c) Equivalent length of Fittings and Valves for Schedule 40 Steel Pipe in Feet is <br />deleted. <br />Notes: <br />1. All service connections (except fire service connections) shall be made downstream <br />of the restriction in the domestic service line. <br />2. The one-half ('/z) inch restrictor and both Tees shown on this drawing shall be on the <br />outside of the house and shall be visible from the street unless a letter of exemption is <br />on file with the Livermore-Pleasanton Fire Department, Fire Prevention Bureau. <br />3. Sizes of piping may vary per plans. Size of restrictor shall always be one-half (1/2) <br />inch. <br />46 <br />