Laserfiche WebLink
Ordinance No. 2197 <br /> Exhibit B <br /> Page 24 <br /> 6004.1.15 Inert gas purge system. Gas systems shall be provided with dedicated inert gas <br /> purge systems. A dedicated inert gas purge system may be used to purge more than one gas, <br /> provided the gases are compatible. Purge gas systems inside buildings shall be located in an <br /> approved gas cabinet unless the system operates by vacuum demand. <br /> Exception: Refrigeration systems. <br /> 20.24.440 CFC Section 6004.1.16 added — Seismic shutoff valve. <br /> Section 6004.1.16 is added to read: <br /> 6004.1.16 Seismic shutoff valve. An automatic seismic shut-off valve, which is of a fail-safe to <br /> close design, shall be provided to shutoff the supply of highly toxic, toxic and moderately toxic <br /> gases with an LC50 less than 3,000 parts per million upon a seismic event within 5 seconds of a <br /> horizontal sinusoidal oscillation having a peak acceleration of 0.3G (1.47m/sec2) and a period of <br /> 0.4 seconds. <br /> 20.24.450 CFC Section 6004.1.17 added — Fittings and connections. <br /> Section 6004.1.17 is added to read: <br /> 6004.1.17 Fittings and connections. Fittings and connections shall be located in a gas cabinet, <br /> exhausted enclosure, gas room or exhausted valve manifold box. <br /> Exception: Welded connections. <br /> 20.24.460 CFC Section 6004.2 amended — Indoor storage and use. <br /> Section 6004.2 is hereby amended to read: <br /> 6004.2 Indoor storage and use amended. The indoor storage or use of highly toxic, toxic and <br /> moderately toxic compressed gases shall be in accordance with Sections 6004.2.1 through <br /> 6004.2.2.10.4. <br /> 20.24.470 CFC Section 6004.2.1 amended —Applicability. <br /> Section 6004.2.1 is hereby amended to read: <br /> 6004.2.1 Applicability. The applicability of regulations governing the indoor storage and use of <br /> highly toxic, toxic and moderately toxic compressed gases shall be in accordance with Sections <br /> 6004.2.1.1 through 6004.2.1.5. <br /> 20.24.480 CFC Section 6004.2.1.1 amended —Quantities not exceeding the maximum <br /> allowable quantity per control area. <br /> Section 6004.2.1.1 is hereby amended to read: <br /> 6004.2.1.1 Quantities not exceeding the maximum allowable quantity per control area. The <br /> indoor storage or use of highly toxic and toxic compressed gases in amounts not exceeding the <br /> maximum allowable quantity per control area set forth in Table 5003.1.1(2) shall be in accordance <br /> with Sections 5001, 5003, 6001, 6004.1, 6004.2.1.4 and 6004.2.1.5. <br /> 20.24.490 CFC Section 6004.2.1.4 added — Quantities not exceeding minimum threshold <br /> quantity per control area. <br /> Section 6004.2.1.4 is added to read: <br />