My WebLink
|
Help
|
About
|
Sign Out
ORD 2197
City of Pleasanton
>
CITY CLERK
>
ORDINANCES
>
2101 - 2200
>
ORD 2197
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
6/30/2023 4:22:26 PM
Creation date
10/23/2019 12:23:28 PM
Metadata
Fields
Template:
CITY CLERK
CITY CLERK - TYPE
ORDINANCES
DOCUMENT DATE
10/15/2019
DESTRUCT DATE
PERMANENT
NOTES
BUILDING CODE
Tags
Ordinance
Description:
Ordinance
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
42
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Ordinance No. 2197 <br /> Exhibit B <br /> Page 23 <br /> 6004.1.9 Local gas shut off. Manual activation controls shall be provided at locations near the <br /> point of use and near the source, as approved by the fire code official. The fire code official may <br /> require additional controls at other places, including, but not limited to, the entry to the building, <br /> storage or use areas, and emergency control stations. Manual activated shut-off valves shall be <br /> of a fail-safe-to-close design. <br /> 20.24.380 CFC Section 6004.1.10 added — Exhaust ventilation monitoring. <br /> Section 6004.1.10 is added to read: <br /> 6004.1.10 Exhaust ventilation monitoring. For highly toxic gases, toxic and moderately toxic <br /> gases exceeding minimum threshold quantities, a continuous monitoring system shall be provided <br /> to assure that the required exhaust ventilation rate is maintained. The system shall monitor actual <br /> air flow in the exhaust system. The monitoring system shall initiate a local alarm. The alarm shall <br /> be both visual and audible and shall be designed to provide warning both inside and outside of <br /> the interior storage, use, or handling area. <br /> 20.24.390 CFC Section 6004.1.11 added — Emergency response plan. <br /> Section 6004.1.11 is added to read: <br /> 6004.1.11 Emergency response plan. If the preparation of an emergency response plan for the <br /> facility is not required by any other law, responsible persons shall prepare, or cause to be <br /> prepared, and filed with the fire code official, a written emergency response plan. If the <br /> preparation of an emergency response plan is required by other law, a responsible person shall <br /> file a copy of the plan with the fire code official. <br /> 20.24.400 CFC Section 6004.1.12 added — Emergency Response Liaisons. <br /> Section 6004.1.12 is added to read: <br /> 6004.1.12 Emergency Response Liaisons. Responsible persons shall be designated and <br /> trained to be liaison personnel for the Livermore-Pleasanton Fire Department. There persons <br /> shall aid the Fire Department in preplanning emergency responses and understanding the <br /> materials and operations utilizing the gases. <br /> 20.24.410 CFC Section 6004.1.13 added — Emergency Drills. <br /> Section 6004.1.13 is added to read: <br /> 6004.1.13 Emergency Drills. Emergency drills of the on-site emergency response personnel <br /> and liaisons shall be conducted on a regular basis but not less than every six months. Records <br /> of drills conducted shall be maintained for three years. <br /> 20.24.420 CFC Section 6004.1.14 added — Cylinder leak testing. <br /> Section 6004.1.14 is added to read: <br /> 6004.1.14 Cylinder leak testing. Cylinders shall be tested for leaks immediately upon delivery <br /> and again immediately prior to departure. Testing shall be approved by the fire code official in <br /> accordance with appropriate nationally recognized industry standards and practices, if any. <br /> Appropriate remedial action shall be immediately undertaken when leaks are detected. <br /> 20.24.430 CFC Section 6004.1.15 added — Inert gas purge system. <br /> Section 6004.1.15 is added to read: <br />
The URL can be used to link to this page
Your browser does not support the video tag.