Laserfiche WebLink
Flammable Any amount 200 <br /> Highly toxic Any amount Any amount <br /> Nonflammable 200 200 <br /> Oxidizer (include. Oxygen) 200 200 <br /> <br /> All quantities are in cubic feet @ standard temperature and pressure <br /> © See Article 75. <br /> <br /> 20.24.080 Table 102 - C - amended <br /> <br /> UFC Table 105-C <br /> <br /> Other hazardous materials subject to California Health <br /> and Safety Code, Title 19, Chapter 6.95: <br /> <br /> (c) Liquid hazardous materials--55 gallons or more <br /> (d) Solid hazardous materials--500 pounds or more <br /> (e) Compressed gas (any) -- 200 cubic feet or more <br /> <br />20.24.090 UFC Table 105-D added--Storage Limitations of Hazardous Materials - Group R, <br />Division 3 Occupancies: <br /> <br />Table 105-D is added as follows: <br /> <br />Outside storage of Flammable Liquids-maximum quantity = 30 gallons <br />Flammable liquids are gasoline, aviation fuel, etc. <br />Outdoor storage of combustible liquids-maximum quantity = 55 gallons <br />Combustible liquids are diesel fuel, kerosene, etc. <br />Outdoor storage of compressed and liquified flammable gas-maximum quantity = 15 gallons for <br />liquefied gases and 540 cubic feet (CF) for compressed gas. Compressed flammable gases are propane, <br />compressed natural gas (CNG), etc. <br /> <br />20.24.100 UFC Section 207-7 amended--Prevention of False Alarms: <br /> <br />Section 207-F is amended by adding the following to the Uniform Fire Code to read: <br /> <br />Section 207-F: False alarms <br />1. It is unlawful for any property owner or licensed contractor to fail to notify the police/fire <br />department dispatch center prior to any test, installation, repair, modification, addition, or <br /> <br /> 48 <br /> <br /> <br />