Laserfiche WebLink
406.2 Minimum pipe size shall be 3/4 inch for copper or brass, and 3/4 inch for plastic <br />(CPVC). <br /> <br />406.3 *To size piping for systems connected to a city water supply, the hydraulically calculated <br />or pipe size method is approximate method is acceptable. <br /> <br />406.3.1.1 Establish system flow rate in accordance with Sec 9.401. <br />406.3.2 Determine water pressure in the street. <br />406.3.3 Select pipe sizes. <br />406.3.4 Deduct meter pressure. <br /> <br />406.3.5 Deduct pressure loss for elevation. (Building height above street feet x 0.434 = <br />psi), (Building height above street in meters x 0.098 - bars). <br /> <br />406.3.6 Deduct pressure losses from city main to control valve by multiplying friction <br />loss per foot by the total length(s) of pipe in feet (m). (Include all fittings). <br /> <br />406.3.7 Deduct pressure losses for piping within building by multiplying friction loss per <br />foot by the total length in feet (m) of each size of pipe between the control valve, check valves, <br />flow switch and the farthest sprinkler. <br /> <br />406.3.8 Deduct valve(s) and fitting pressure losses. Count the valves and fittings from the <br />control valve to the farthest sprinkler. Determine the equivalent length for each valve and fitting <br />as shown in Table IV and add these values to obtain the total equivalent length for each pipe <br />size. <br /> <br />406.3.9 In multi-level buildings, these steps shall be repeated to size piping for each floor. <br /> <br />406.3.10 If the remaining pressure is less than the operating pressure established by the <br />testing laboratory for the sprinkler being used, a redesign is necessary. If this pressure is higher <br />than required, smaller piping may be used when justified by calculations. <br /> <br /> 406.3.11 The remaining piping shall be sized the same as the piping to the farthest <br /> sprinkler unless smaller sizes are justified by calculations. <br /> <br /> Exception: For sprinklered dwellings manufactured off site, the minimum pressure needed to satisfy <br /> the system design criteria on the system side of the meter shall be specified on a data plate by the <br /> manufacturer. <br /> <br /> 23 <br /> <br /> <br />