Ordinance No. 2083 <br /> Page 30 <br /> 5003.5.2 Ventilation ducting. Product conveying ducts for venting hazardous materials <br /> operations shall be labeled with the hazard class of the material being vented and the <br /> direction of flow. <br /> 20.24.160 CFC Section 5003.5.3 added — H Occupancies. <br /> Section 5003.5.3 is added to read: <br /> 5003.5.3 H Occupancies. In "H" occupancies, all piping and tubing may be required to <br /> be identified when there is any possibility of confusion with hazardous materials <br /> transport tubing or piping. Flow direction indicators are required. <br /> 20.24.170 CFC Section 5003.13 added — Automatic Filling of Tanks. <br /> Section 5003.13 is added to read: <br /> 5003.113 Automatic Filling of Tanks. Systems that automatically fill flammable or <br /> combustible liquid tanks shall be equipped with approved overfill protection, that <br /> sends an alarm signal to a location that is normally occupied during normal business <br /> hours and immediately stops the filling of the tank. The alarm signal and automatic <br /> shutoff shall be tested in a manner acceptable to the fire code official on an annual <br /> basis and records of such testing shall be maintained on-site for a period of five (5) <br /> years. <br /> Exception: Emergency generator tanks. <br /> 20.24.180 CFC Section 5608.2 added — Prohibition of Fireworks. <br /> 5608.2 Prohibition of Fireworks. It shall be unlawful for any person, corporation, or <br /> entity to possess, store, offer for sale, expose for sale, sell at retail or wholesale, use or <br /> explode any fireworks. <br /> Exception: The use of fireworks as part of a professional display, operated by a <br /> California State licensed pyrotechnic operator as set forth in Section 5601.1 <br /> 20.24.190 CFC Section 5608.3 added — Seizure of Fireworks. <br /> 5608.3 Seizure of Fireworks. The Fire Chief shall seize, take, remove or cause to be <br /> removed at the expense of the owner all stocks of fireworks offered or exposed for sale, <br /> stored or held in violation of this article. <br /> 20.24.200 CFC Section 5704.2.7.5.8 amended - Exception. <br /> Section 5704.2.7.5.8, Exception, is amended to read: <br />