Laserfiche WebLink
Section 903.2 Where required. Approved automatic fire extinguishing systems in new <br /> buildings and structures shall be as provided in all new occupancies and locations. <br /> Exception: Group U occupancies that do not exceed 400 square feet of floor area. <br /> 20.24.120 CFC Section 903.3.1.2 amended - NFPA 13R Sprinkler Systems. <br /> Section 903.3.1.2 is amended to read: <br /> 903.3.1.2 NFPA 13R sprinkler systems. Automatic sprinkler systems in Group R <br /> occupancies up to and including four stories in height shall be permitted to be installed <br /> throughout in accordance with NFPA 13R as amended in Chapter 47 and the following; <br /> Sprinklers shall be provided in all attic areas. <br /> 20.24.130 CFC Section 903.3.1.3 amended — NFPA 13D sprinkler systems. <br /> Section 903.3.1.3 is amended to read: <br /> 903.3.1.3 NFPA 13D sprinkler systems. Residential automatic fire sprinklers systems <br /> shall be installed in accordance to NFPA 13D in all new one- and two- family dwellings. <br /> In addition, the fire-sprinkler system shall be designed and sprinklers shall be installed <br /> in the following additional locations: <br /> 1. Attic shall be provided with intermediate temperature-rated residential fire <br /> sprinklers for detection coverage, and located at a spacing equivalent to 30 feet <br /> by 30 feet centers and a maximum distance of 15 feet from outside walls. <br /> 2. Fire sprinklers shall be provided in garages. Fire sprinklers shall be intermediate <br /> rated, quick response type, with a maximum coverage area of 130 square feet <br /> per sprinkler. <br /> 20.24.140 CFC Section 5003.2.10 added — Biodiesel and methanol equipment. <br /> Section 5003.2.10 is added to read: <br /> 5003.2.10 Biodiesel and methanol equipment. Biodiesel and methanol <br /> manufacturing/processing equipment shall be listed or approved. Such equipment shall <br /> at a minimum adequately address electrical system, materials of construction, <br /> ventilation, seismic and process control and shut-down safety issues. <br /> 20.24.150 CFC Section 5003.5.2 added —Ventilation ducting. <br /> Section 5003.5.2 is added to read: <br />