• Fire flow and duration shall be provided in accordance with 2010 CFC <br /> Appendix B. <br /> • Installation drawings can be identified as deferred submittal for these <br /> plans. The underground pipeline contractor shall submit a minimum of <br /> three (3) sets of installation drawings to the Building Department, to be <br /> reviewed by the Fire Prevention Bureau. The plans shall have the <br /> contractor's wet stamp indicating the California contractor license type, <br /> license number and must be signed. No underground pipeline inspections <br /> will be conducted prior to issuance of approved plans. <br /> • All underground fire protection work shall require a California contractor's <br /> license type as follows: C-16, C-34, and C-36 or A. <br /> • All field-testing and inspection of piping joints shall be conducted prior to <br /> covering of any pipeline. <br /> • Electrical conduit shall be provided to each fire protection system control <br /> valve including all valve(s) at the water connections. The Livermore- <br /> Pleasanton Fire Department requires electronic supervis on of all valves <br /> for automatic sprinkler systems and fire protection systems. <br /> Building and Safety Division <br /> 117. The principles of Universal Design shall be incorporated into the apartment units <br /> wherever possible. Unless otherwise determined by the Chief Building Official, all <br /> required adaptable dwelling units shall provide the following features whenever <br /> possible: <br /> a. Audible & visual doorbell within unit. <br /> b. Balcony/patio at same floor level as unit. <br /> c. Windows for viewing shall have a 36" maximum sill height. <br /> d. 44" minimum hallway width and 32" minimum clear door opening width for <br /> all doorways within units. <br /> e. Lever type handles on all doors. <br /> f. An 18" minimum clear floor space beside door on pull side at latch jamb. <br /> g. All receptacle or other outlets, 18" minimum height above finished floor. <br /> h. Rocker type light switches 40"- 48" above finish floor, and thermostats 48" <br /> maximum height. <br /> PUD-87, Auf der Maur/ Rickenbach /Vintage City Council <br /> Page 19 of 39 <br />