2. Piping and tubing shall not be located within corridors, within any portion of a <br /> means of egress required to be enclosed in fire - resistance -rated construction or <br /> in concealed spaces in areas not classified as Group H Occupancies. <br /> Exception: Piping and tubing within the space defined by the walls of corridors <br /> and the floor or roof above or in concealed space above other occupancies <br /> when installed in accordance with Section 415.8.6.3 of the California Building <br /> Code as required for Group H, Division 5 Occupancies. <br /> 3. All primary piping for toxic, highly toxic and moderately toxic gases shall pass a <br /> helium leak test of 1x10 -9 cubic centimeters /second where practical, or shall <br /> pass testing in accordance with an approved, nationally recognized standard. <br /> Tests shall be conducted by a qualified "third party" not involved with the <br /> construction of the piping and control systems. <br /> 20.24.280 CFC Section 2703.2.10 added — Biodiesel and methanol equipment. <br /> Section 2703.2.10 is added to read: <br /> 2703.2.10 Biodiesel and methanol equipment. Biodiesel and methanol <br /> manufacturing /processing equipment shall be listed or approved. Such equipment shall <br /> at a minimum adequately address electrical system, materials of construction, <br /> ventilation, seismic and process control and shut -down safety issues. <br /> 20.24.290 CFC Section 2703.5.2 added — Ventilation ducting. <br /> Section 2703.5.2 is added to read: <br /> 2703.5.2 Ventilation ducting. Product conveying ducts for venting hazardous materials <br /> operations shall be labeled with the hazard class of the material being vented and the <br /> direction of flow. <br /> 20.24.300 CFC Section 2703.5.3 added — H Occupancies. <br /> Section 2703.5.3 is added to read: <br /> 2703.5.3 H Occupancies. In "H" occupancies, all piping and tubing may be required to <br /> be identified when there is any possibility of confusion with hazardous materials <br /> transport tubing or piping. Flow direction indicators are required. <br /> 20.24.310 CFC Section 2703.9.8 amended — Separation of incompatible <br /> materials. <br /> Section 2703.9.8 is amended to read: <br /> 2703.9.8 Separation of incompatible materials. Incompatible materials in storage <br /> and storage of materials that are incompatible with materials in use shall be separated. <br /> 64 <br />