Article 625-29 (1) of the California Building Standards Code 2001 <br /> Edition (24 C.C.R.), and including by reference the <br /> National Electrical Code, is added to read as follows: <br /> <br />(1) Table Values for Ventilation. <br />For supply voltages and currents specified in Table 625- <br />29(D)(1) or 625-29(D)(2). The minimum ventilation <br />requirements shall be as specified in Table 625-29(D)(1) or <br />Table 625-29(D)(2) for each of the total number of electric <br />vehicles that can be charged at one time. <br /> <br />Table 625-29(D)(1) Minimum Ventilation Required in Cubic Meters per Minute <br />(m3/min) for Each of the Total Number of Electric Vehicles That Can Be Charged at One <br />Time. <br /> <br /> Branch Circuit Voltage <br /> Single Phase Three Phase <br />Branch 120V 208V 240V or 208V or 240V 480V or 600V or <br />Circuit 120/240V 208Y/120V 480Y/277V 600Y/347V <br />Ampere <br />Rating <br />15 1.1 1.8 2.1 ........ <br />20 1.4 2.4 2.8 4.2 4.8 9.7 I2.0 <br />30 2.1 3.6 4.2 6.3 7.2 15.0 18.0 <br />40 2.8 4.8 5.6 8.4 9.7 19.0 ! 24.0 <br />50 3.5 6.1 7.0 10.0 12.0 24.0 30.0 <br />60 4.2 7.3 8.4 13.0 15.0 29.0 36.0 <br />100 7.0 12.0 14.0 21.0 24.0 48.0 60.0 <br />150 ...... 31.0 36.0 73.0 91.0 <br />200 ...... 42.0 48.0 97.0 120.0 <br />250 ...... 52.0 60.0 120.0 150.0 <br />300 ...... 63.0 73.0 145.0 180.0 <br />350 ...... 73.0 85.0 170.0 210.0 <br />400 ...... 84.0 97.0 195.0 240.0 <br /> <br />Table 625-29(D)(2) Minimum Ventilation Required in Cubic Meters per Minute (m3/min) <br />for Each of the Total Number of Electric Vehicles That Can Be Charged at One Time. <br /> Branch Circuit Voltage <br /> Single Phase Three Phase <br />Branch 120V 208V 240V or 208V or 240V 480V or 600V or <br />Circuit 120/240V 208Y/120V 480Y/277V 600Y/347V <br />Ampere <br />Rating <br />15 37 64 74 ...... <br /> <br />60 <br /> <br /> <br />