Laserfiche WebLink
CHAPTER 4-System Design - amended <br />Section 4-2.6 is added to read: <br /> <br />(a) Pilot fire sprinkler protection and fire detection shall be provided in all <br />attic spaces. Pilot fire sprinkler locations shall be near heat or fire sources, <br />i.e., HVAC equipment, water heaters, kitchen duct/exhaust penetrations, <br />or other electrical or gas fired equipment, etc. <br /> <br />(b) Pilot fire sprinkler sprig ups or risers shall be braced in accordance <br />with pipe manufacturers recommendations for vertical support and within <br />4 to 6 inches of the fire sprinkler when the vertical riser exceeds 30 inches <br />vertically. <br /> <br />Chapter 4-System Design - amended <br /> <br />Section 4-6 Location of Sprinklers is amended to read: <br /> <br />Sprinklers shall be installed in all areas. <br /> <br />Exception #1: Sprinklers may be omitted from bathrooms not exceeding <br />55 square feet (5.1 m) with non-combustible fixtures. <br /> <br />Exception #2: Sprinklers may be omitted from small closets where the <br />least dimension does not exceed 3 feet. (0.9 M), the area does not exceed <br />24 square feet (2.2 m), and the walls and ceiling are surfaced with non- <br />combustible materials. <br /> <br />Exception #3: Sprinklers may be omitted from attics and crawl spaces <br />which are not used or intended for living purposes or storage in buildings <br />with no more than four (4) dwelling units, except pilot sprinklers are <br />required as per section 4-2.6 (above). <br /> <br />Note: See Chapter 4 System Design for provisions in buildings with five <br />(5) to fifteen (15) dwelling units not exceeding twelve thousand square <br />feet (12,000 square feet). <br /> <br />CHAPTER 4-System Design - amended <br /> <br />Table 4-4.3(a) Pressure Losses in psi/ft, for Schedule 40 Steel <br />Pipe(C=120) and Table 4-4.3(c) Equivalent length of Fittings and Valves <br />for Schedule 40 Steel Pipe in Feet is deleted. <br /> <br />Notes: <br /> <br />29 <br /> <br /> <br />