Laserfiche WebLink
(16 764 mm) or more above the lowest level of fire <br />department vehicle access. <br /> <br />EXCEPTIONS: 1. Airport control towers. <br /> <br />20.08.049 -Amended- City of Pleasanton Sprinkler Standard 9-3: <br /> <br />UBC Section 902-Standards of Quality <br />1. Fire -Extinguishing system <br />1.2 UBC Standard 9-3 -amended to reference NFPA 13D- <br />1999 Ed. <br /> <br />Installation of Sprinkler Systems in Residential <br />Occupancies. <br /> <br />UBC Section 902 amended--Standards of Quality <br /> <br />Section 902 1. Fire- Extinguistfing System <br /> <br />Section 902 1. -1.2 is amended to read: <br /> <br />UBC Standard 9-3 is amended to adopt National Fire Protection <br />Association (NFPA) 13D-1999 Edition. This Standard includes <br />installation of fire sprinkler systems in buildings up to fifteen (15) units <br />and up to a maximum of twelve thousand (12,000) square feet maximum. <br /> <br />Chapter 1-General Information amended- <br /> <br />Section 1-1 Scope is amended to read: <br /> <br />This standard describes the requirements for the mechanical and <br />performance properties of the sprinkler itself. It also describes the <br />Section 1-5.4 All systems shall be tested for leakage at 200 psi for two (2) <br />hours. <br /> <br />Chapter 1-General Information - added <br /> <br />Section 1-5.6 is added to read: <br /> <br />Section 1-5.6 All sprinkler piping shall be either non-ferrous metallic pipe <br />(copper, or brass) or CPVC. All piping above the flow switch should be <br />protected by sheet rock or plywood. Note: No ferrous (black iron, iron or <br /> <br />26 <br /> <br /> <br />