Laserfiche WebLink
Attachment 1 Exhibit B <br /> identification label must include the product/waste name and flow direction indicator. Labels to be <br /> placed no less than once every 20 feet of piping and at changes of direction. <br /> 20.24.230 CFC Section 5003.14 added—Automatic Filling of Tanks. <br /> Section 5003.14 is added to read: <br /> 5003.13 Automatic Filling of Tanks. Systems that automatically fill flammable or combustible <br /> liquid tanks shall be equipped with approved overfill protection that sends an alarm signal to a <br /> location that is normally occupied during normal business hours and immediately stops the filling of <br /> the tank. The alarm signal and automatic shutoff shall be tested in a manner acceptable to the fire <br /> code official on an annual basis and records of such testing shall be maintained on-site for a period of <br /> five(5)years. <br /> Exception: Emergency generator tanks. <br /> 20.24.240 CFC Section 5005.5 added —Emergency Alarms,supervision and monitoring <br /> Section 5005.5 is added as follows: <br /> 5005.5 Emergency alarms,supervision and monitoring. Emergency alarms, supervision and <br /> monitoring shall be provided in accordance with Sections 5004.9 and 5004.10. <br /> Page 32 of 64 <br />