Attachment 1 Exhibit B <br /> 2. The fire department may charge fees that reasonably constitute the cost of response to <br /> unwanted alarms when it is determined that the report is malicious,or resulting from the failure to <br /> maintain a fire protection alarm system. <br /> 20.24.160 CFC Section 903.2 amended—Automatic Sprinkler Systems <br /> 903.2 is deleted and replaced with the following: <br /> 903.2 Where required. <br /> 1. Automatic fire extinguishing systems shall be provided in all new buildings and structures, <br /> including any detached or attached structure added to a parcel of land already containing automatic <br /> extinguishing system protected buildings. <br /> Exception: <br /> a. Detached U Occupancies, other than trash enclosures,that do not exceed 400 square feet of <br /> floor area. <br /> b. Trash enclosures that have been exempted by the fire code official or that meet the following <br /> conditions: <br /> i. The enclosure, including the cover and door, are constructed of non-combustible <br /> materials. <br /> ii. The enclosure does not exceed 180 square feet in size <br /> iii. The enclosure is stand-alone structure, be a minimum of 20 feet from adjacent <br /> buildings and a minimum of 10 feet from property line(s). <br /> iv. The enclosure is used exclusively for waste garbage contained within approved trash <br /> containers. No outdoor storage is permitted within the trash enclosure, <br /> c. Photo Voltaic Arrays covering parking stalls only. <br /> 2. Existing commercial or industrial buildings not currently provided with automatic fire extinguishing <br /> systems shall be provided with an automatic fire extinguishing systems as follows: <br /> a. When modification to the building results in a 50%or greater increase of the total floor area <br /> of the building or brings the over total of floor area of the building to more than 8,000 square <br /> feet, the entire building shall be provided with an automatic fire extinguishing system. <br /> Exception: Additions providing accessory storage space not greater than 500 square feet <br /> in area to an existing non-fire sprinklered building or solely for the purpose of providing <br /> accessibility shall not result in a requirement that the building be provided with an <br /> automatic extinguishing system. <br /> b. When a change in occupancy classification results in an increased fire hazard or risk to <br /> business operations or increased life safety hazard of the occupants,the new occupancy and <br /> all fire areas that the new occupancy exits through shall be provided with an automatic <br /> extinguishing system. <br /> Exception: Public assembly occupancies not exceeding an occupant load of 150, <br /> whether occupying an entire building or a portion of a building. <br /> 3. Existing residential buildings not currently provided with automatic fire extinguishing systems shall <br /> be provided with an automatic fire extinguishing systems as follows: <br /> a. When a modification or modifications to the building results in a 50%or greater increase of <br /> the total original approved floor area of the building <br /> Page 29 of 64 <br />