My WebLink
|
Help
|
About
|
Sign Out
14
City of Pleasanton
>
CITY CLERK
>
AGENDA PACKETS
>
2007
>
120407
>
14
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
11/28/2007 2:27:21 PM
Creation date
11/28/2007 12:27:52 PM
Metadata
Fields
Template:
CITY CLERK
CITY CLERK - TYPE
STAFF REPORTS
DOCUMENT DATE
12/4/2007
DESTRUCT DATE
15 Y
DOCUMENT NO
14
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
109
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
20.08.055 Section 1910.1 amended -Minimum Slab Provisions. <br />Section 1910.1 of the California Building Standards Code 2007 Edition, (24 <br />C.C.R.), and including by reference the International Building Code, 2006 <br />Edition, Volumes 1 and 2 is amended to read as follows: <br />1910.1 General. The thickness of concrete floor slabs supported directly on the <br />ground shall not be less than 31/2" (89mm). A 6-mil (.006 inch; .015mm) <br />polyethylene vapor retarder with joints lapped not less than 6 inches (152mm) <br />shall be placed between the base course or subgrade and the concrete floor <br />slab, or other approved equivalent methods or materials shall be used to retard <br />vapor transmission through the floor slab. As a minimum and in all cases where <br />a slab is to be placed inside of a building the slab shall be reinforced with not <br />less than six inches by six inches ten gauge welded wire mesh or an approved <br />alternate installed at mid height of the slab. <br />In slabs under habitable spaces a 4 inch (10 mm) crushed rock capillary water <br />barrier shall be provided under the minimum 6 mil vapor retarder. A minimum of <br />2 inches (5 mm) of clean sand shall be placed over the 6 mil vapor retarder <br />below the slab. (Balance of section to remain). <br />20.08.056 -This Section is Deleted. <br />20.08.057 -This Section is Deleted. <br />20.08.058 Section 704.5 amended -Fire-resistance ratings. <br />Section 704.5 Fire-resistance ratings of the California Building Standards Code <br />2007 Edition, (24 C.C.R.), and including by reference the International Building <br />Code, 2006 Edition, Volumes 1 and 2 is amended to read as follows: <br />704.5 Fire-resistance ratings. For other than high-rise buildings, Group A, E, H, 1, <br />L and R occupancies and other applications listed in Section 111 regulated by <br />the Office of the State Fire Marshal, and in general and for all occupancies not <br />regulated by the State Fire Marshall exterior walls shall be fire-resistance rated in <br />accordance with Tables 601 and 602. The fire-resistance rating of exterior walls <br />for Groups R-2, R-3 and U occupancies with a fire separation distance of 5 feet <br />(1524 mm) or less shall be rated for exposure to fire from both sides. All other <br />occupancies not regulated by the State Fire Marshall with a fire separation <br />distance of 10 feet (3048 mm) or less shall be rated for exposure to fire from <br />both sides. <br />For high-rise buildings, Group A, E, H, 1, L and R occupancies and other <br />si <br />
The URL can be used to link to this page
Your browser does not support the video tag.