Laserfiche WebLink
1. Specific Plan Water System Concept <br />The City will provide water for all uses , except the irrigation of vineyards and other <br />agricultural activities. Distribution facilities must satisfy minimum design criteria as <br />specified in the "Hillside Water Pressure Zone Master Plan" and be constructed to the <br />specifications of the Public Works Department. The following is a summary of special <br />considerations which must be addressed in providing water service within the Plan Area. <br />a. Water Pressure <br />Water connections at different elevations will require different strategies to meet <br />established pressure criteria . The majority of the connections will fall within the <br />normal elevation boundaries of the City's Bonde Zone (390 to 540 feet). It is <br />possible to serve water connections within this range by integrating into the <br />Bonde Zone and providing additional storage and pumping facilities. <br />The Plan Area has been divided into four elevation bands, as shown in <br />Figure VI-2 . Each band has different service considerations . Starting from the <br />lowest elevation band, the methods needed to meet the water pressure criteria are <br />as follows: <br />• Below Elevation 390: The normal lower service level boundary of the <br />Bonde Zone is 390 feet. A portion of Lot 18 located along the north edge <br />of the Plan Area adjoining the Arroyo del Valle is situated as much as <br />seven feet below this boundary . Localized pressure could approach <br />120 pounds per square inch (psi), but would not exceed the 125 psi <br />maximum allowable limit. A majority of the affected area is designated <br />on the land use plan (Figure IV-2) for Vineyard use. However a limited <br />number of residential units may be affected . Pressure concerns for these <br />homes shall be mitigated by requiring the installation of pressure reduc ing <br />valves (PRV's) for all connections . Current City standards requ ire the use <br />of this equipment in all situations where localized water pressu re is above <br />80 psi. <br />• Between Elevation 390 and 475: Service connections within this band will <br />also experience pressures exceeding 80 psi , and will therefore require the <br />installation of PRV's . <br />• Between Elevation 475 and 540 : No special water pressure measures will <br />be needed to serve the planned and existing homes located within this <br />band . <br />75