Laserfiche WebLink
Ordinance No. 2241 <br /> Page 35 of 60 <br /> Section 6004.3.2 is hereby amended to read: <br /> 6004.3.2 General outdoor requirements.The general requirements applicable to the outdoor storage <br /> and use of highly toxic,toxic and moderately toxic gases shall be in accordance with Sections 6004.3.2.1 <br /> through 6004.3.2.4. <br /> Moderately toxic gases with an LC50 equal to or less than 3000 parts per million shall comply with the <br /> requirements for toxic gases in Sections 5001, 5003, 6001, 6004.1 and 6004.3. <br /> Moderately toxic gases with an LC50 more than 3000 parts per million but not greater than 5000 parts per <br /> million and exceeding the maximum threshold quantity,as determined by 6004.1.6, shall comply with the <br /> requirements for toxic gases in Sections 5001, 5003, 6001, 6004.1 and 6004.3.2.1 through 6004.3.2.4. <br /> Moderately toxic gases shall not be considered as toxic gases for maximum allowable quantities <br /> determinations under Table 5003.1.1(2). <br /> 20.24.610 CFC Section 6004.3.3 amended—Outdoor storage weather protection for portable tanks <br /> and cylinders. <br /> Section 6004.3.3 is hereby amended to read: <br /> 6004.3.3 Outdoor storage weather protection for portable tanks and cylinders. Weather protection in <br /> accordance with Section 5004.13 shall be provided for portable tanks and cylinders located outdoors and <br /> not within gas cabinets or exhausted enclosures. The storage area shall be equipped with an approved <br /> automatic sprinkler system in accordance with Section 5004.5.(Exceptions deleted) <br /> i <br /> i <br /> i <br /> i <br /> I <br /> i <br />