Laserfiche WebLink
Ordinance No. 2217 <br /> Page 20 <br /> 75. EMERGENCY RADIO COVERAGE: Emergency responder radio coverage is required in <br /> accordance with section 510 of the fire code. (Project Specific Condition) <br /> 76. SPRINKLERS: A sprinkler system is required in accordance with section 903 of the fire <br /> code with local ordinances. (Project Specific Condition) <br /> 77. STANDPIPES: A standpipe system is required in accordance with section 905 of the fire <br /> code (as applicable). (Project Specific Condition) <br /> 78. FIRE FLOW: Fire flow shall be in accordance with appendix B of the fire code with a 50 <br /> percent reduction for sprinklers. (Project Specific Condition) <br /> 79. FIRE HAZARDS: The project developer shall keep the site free of fire hazards from the <br /> start of lumber construction until the final inspection. <br /> 80. FIRE PROTECTION FACILITIES: Prior to any construction framing, the applicant shall <br /> provide adequate fire protection facilities, including, but not limited to a water supply and <br /> water flow in conformance to the City's Fire Department Standards able to suppress a <br /> major fire. <br /> 81. WATER FLOW AND CONTROL VALVES: All fire sprinkler system water flow and <br /> control valves shall be complete and serviceable prior to final inspection. Prior to the <br /> occupancy of a building having a fire alarm system, the Fire Department shall test and <br /> witness the operation of the fire alarm system. <br /> 82. ELECTRICAL CONDUIT: Electrical conduit shall be provided to each fire protection <br /> system control valve including all valve(s) at the water connections. The Livermore- <br /> Pleasanton Fire Department requires electronic supervision of all valves for automatic <br /> sprinkler systems and fire protection systems. <br /> 83. LISTED: All commercial, industrial, and multi-family residential occupancies shall have <br /> valve tamper and water flow connected to a listed Central Station Service in accordance <br /> with NFPA 72. Fire Department plan check includes specifications, monitoring, <br /> installation, and alarm company certificates. Fire alarm control panel and remote <br /> annunciation shall be at location(s) approved by the Fire Prevention Bureau. All systems <br /> shall be point identified by individual device and annunciated by device type and point. <br /> 84. HAZARDOUS MATERIALS: Should any operation or business activity involve the use, <br /> storage or handling of hazardous materials, the firm shall be responsible for contacting <br /> the Livermore-Pleasanton Fire Department prior to commencing operations. Please <br /> contact the Hazardous Materials Coordinator at 925/454-2361. <br /> 85. FIRE HYDRANTS: Fire hydrants shall be installed at spacing not greater than 300 feet in <br /> industrial and commercial developments. Fire hydrants shall be installed at spacing not <br /> greater than 400 feet in residential developments. <br /> 86. FIRE LANE MARKING: On-site access ways, turn arounds, and internal drives shall be <br /> designated as fire lanes and identified as such by red curb striping and posted with signs <br /> at locations approve by the Fire Department. Signs shall be according to State standards <br /> and read "No Parking — Fire Lane" and must be shown on the plans. The red curb <br /> striping, sign location(s), and sign language shall be included in the building permit <br />