Laserfiche WebLink
Moderately toxic gases with an LC50 equal to or less than 3000 parts per million shall comply <br />with the requirements for toxic gases in Sections 5001, 5003, 6001, 6004.1 and 6004.3. <br />Moderately toxic gases with an LC50 more than 3000 parts per million but not greater than 5000 <br />parts per million and exceeding the maximum threshold quantity, as determined by 6004.1.6, shall <br />comply with the requirements for toxic gases in Sections 5001, 5003, 6001, 6004.1 and <br />6004.3.2.1 through 6004.3.2.4. <br />Moderately toxic gases shall not be considered as toxic gases for maximum allowable quantities <br />determinations under Table 5003.1.1(21. <br />20.24.610 CFC Section 6004.3.3 amended —Outdoor storage weather protection for <br />portable tanks and cylinders. <br />Section 6004.3.3 is hereby amended to read: <br />6004.3.3 Outdoor storage weather protection for portable tanks and cylinders. Weather <br />protection in accordance with Section 5004.13 shall be provided for portable tanks and cylinders <br />located outdoors and not within gas cabinets or exhausted enclosures. The storage area shall be <br />equipped with an approved automatic sprinkler system in accordance with Section 5004.5. <br />f Exceptions deletedl <br />Page 39 of 52 <br />