Based on the information received, there may be additional requirements such <br />as: smoke and heat venting, in -rack sprinklers, increases in sprinkler design <br />criteria, draft curtains, etc. <br />95. Electrical conduit shall be provided to each fire protection system control <br />valve including all valve(s) at the water connections. The Livermore - <br />Pleasanton Fire Department requires electronic supervision of all valves for <br />automatic sprinkler systems and fire protection systems. <br />96.AlI fire sprinkler system water flow and control valves shall be complete and <br />serviceable prior to final inspection. Prior to the occupancy of a building <br />having a fire alarm system, the Fire Department shall test and witness the <br />operation of the fire alarm system. <br />97.AII commercial, industrial, and multi - family residential occupancies shall have <br />valve tamper and water flow connected to an Underwriters Laboratory (UL) <br />listed Central Station Service. Fire Department plan check includes <br />specifications, monitoring certificate(s), installation certificate and alarm <br />company UL certificate. Fire alarm control panel and remote annunciation <br />shall be at location(s) approved by the Fire Prevention Bureau. All systems <br />shall be point identified by individual device and annunciated by device type <br />and point. <br />98. Electrical conduit shall be provided to each fire protection system control <br />valve including all valve(s) at the water connections. The Livermore - <br />Pleasanton Fire Department requires electronic supervision of all valves for <br />automatic sprinkler systems and fire protection systems. <br />99. The following items will be provided prior to any construction above the <br />foundation or slab. NOTE: Periodic inspections will be made for compliance. <br />a. Emergency vehicle access shall be provided to the site. If Public Works <br />Improvements are part of the project to access the site, an emergency vehicle <br />access plan shall be submitted for review and approval. <br />b. Site access shall be provided prior to any construction above the foundation <br />or slab. Based on the Site Plan Approval the access shall be installed. <br />c. Emergency vehicle access shall be a minimum of 20 feet in width. A clear <br />height free of obstructions (power, cable, telephone lines, tree limbs, etc.) <br />shall be provided. This clearance shall be a minimum of 13 feet -6 inches. <br />Inside turning radius of 45 feet and outside turning radius of 55 feet shall be <br />provided. <br />PUD -100 <br />Conditions of Approval (Planning Commission) <br />Chick -fil -A <br />Page 15 <br />