Laserfiche WebLink
Service. Fire Department plan check includes specifications, monitoring <br /> certificate(s), installation certificate and alarm company UL certificate. <br /> 117. Fire alarm control panel and remote annunciation shall be at location(s) approved <br /> by the Fire Prevention Bureau. All systems shall be point identified by individual <br /> device and annunciated by device type and point. <br /> 118. The project developer shall keep the site free of fire hazards from the start of <br /> lumber construction until the final inspection. <br /> 119. Prior to any construction framing, the project developer shall provide adequate fire <br /> protection facilities, including, but not limited to a water supply and water flow in <br /> conformance to the City's Fire Department Standards able to suppress a major <br /> fire. <br /> 120. All fire sprinkler system water flow and control valves shall be complete and <br /> serviceable prior to final inspection. Prior to the occupancy of a building having a <br /> fire alarm system, the Fire Department shall test and witness the operation of the <br /> fire alarm system. <br /> 121. Should any operation or business activity involve the use, storage or handling of <br /> hazardous materials, the firm shall be responsible for contacting the LPFD prior to <br /> commencing operations. Please contact the Hazardous Materials Coordinator at <br /> (925) 454-2361. <br /> 122. The Fire Prevention Bureau reviews building/civil drawings for conceptual on-site <br /> fire mains and fire hydrant locations only. Plan check comments and approvals <br /> DO NOT INCLUDE: <br /> • Installation of the on-site fire mains and fire hydrants. Specific installation <br /> drawings submitted by the licensed underground fire protection contractor <br /> shall be submitted to the Fire Prevention Bureau for approval. <br /> • Backflow prevention or connections to the public water mains. <br /> 123. Electrical conduit shall be provided to each fire protection system control valve <br /> including all valve(s) at the water connections. The Livermore-Pleasanton Fire <br /> Department requires electronic supervision of all valves for automatic sprinkler <br /> systems and fire protection systems. <br /> 124. Hydrant spacing shall be at 400 feet. <br /> 125. Address numbers shall be installed on the front or primary entrance for all <br /> buildings. Minimum building address character size shall be 12" high by 1" stroke. <br /> For buildings located greater than 50 feet from street frontage, the character size <br /> shall be 16" high by 1 '/2" stroke minimum. Where multiple access is provided, <br /> address or tenant space numbers shall be provided on each access door and the <br /> 20 of 31 <br /> L <br />