Laserfiche WebLink
20.24.030 CFC Chapter 1, Division II, Table 105.6.10 amended — Permit Amounts <br />for Cryogenic Fluids. <br />Table 105.6.10 is amended to read: <br />Type of Cryogenic Fluid <br />Cubic feet at NTP <br />Corrosive <br />Any Amount <br />Flammable <br />Any Amount <br />Inert <br />200 <br />Oxidizing (including oxygen) <br />200 <br />Physical or health hazard not indicated above <br />Any amount <br />All other materials subject to HMBP requirements (per <br />material) <br />200 <br />20.24.040 CFC Section 105.6.16 Item 3 amended — Flammable and combustible <br />liquids. <br />Section 105.6.16 Item 3 is amended to read: <br />To store, handle or use Class II or Class IIIA liquids in excess of 25 gallons except for <br />fuel oil in the fuel tanks of portable equipment. <br />20.24.050 CFC Section 105.6.16 Item 12 added - Permit Amounts for Hazardous <br />Materials, Flammable and Combustible Liquids and Gases at <br />Residential Occupancies. <br />Section 105.6.16 Item 12 is added to read: <br />12. Storage of flammable and combustible liquids and flammable gases at Group R <br />occupancies are limited as follows: <br />1. Outside storage of flammable liquids (including gasoline) is limited to 30 <br />gallons. <br />2. Outside storage of combustible liquids (including diesel and kerosene) is <br />limited to 55 gallons. <br />Exception: Emergency generators used for life safety purposes. <br />3. Outside storage of compressed and liquefied flammable gas is limited to 15 <br />gallons or 540 cubic feet. <br />Exceptions: <br />a. Emergency generators used for life safety purposes. <br />b. Facility gas supply for occupancies not provided with natural gases <br />services. Amounts over 1,000 gallons must be approved by the fire <br />official. <br />4. Manufacture of Biodiesel and Methanol at Residential Occupancies. The <br />manufacture of biodiesel and methanol is prohibited in Residential <br />