My WebLink
|
Help
|
About
|
Sign Out
06
City of Pleasanton
>
CITY CLERK
>
AGENDA PACKETS
>
2013
>
091713
>
06
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
9/25/2013 12:21:35 PM
Creation date
9/12/2013 3:38:58 PM
Metadata
Fields
Template:
CITY CLERK
CITY CLERK - TYPE
AGENDA REPORT
DOCUMENT DATE
9/17/2013
DESTRUCT DATE
15Y
DOCUMENT NO
06
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
56
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
In Seismic Design Categories Do, D, and D2 where a grouted masonry stem wall is <br />supported on a concrete footing and stem wall, a minimum of one No. 4 bar shall be <br />installed at not more than 4 feet (1219 mm) on center. The vertical bar shall extend to 3 <br />inches (76 mm) clear of the bottom of the footing and have a standard hook. <br />In Seismic Design Categories Do, D1 and D2, masonry stem walls without solid grout <br />and vertical reinforcing are not permitted. <br />Exception: In detached one- and two- family dwellings which are three stories or less <br />in height and constructed with stud bearing walls, isolated plain concrete footings <br />supporting columns or pedestals are permitted. <br />20.10.110 CRC Section R507.1 amended— Decks <br />Section R507.1 is amended to read as follows: <br />R507.1 Decks. Where supported by attachment to an exterior wall, decks shall be <br />positively anchored to the primary structure and designed for both vertical and lateral <br />loads as applicable. Such attachment shall not be accomplished by the use of toenails <br />or nails subject to withdrawal. Where positive connection to the primary building <br />structure cannot be verified during inspection, decks shall be self- supporting. For <br />exterior balconies with cantilevered framing members, connections to exterior walls or <br />other framing members, shall be designed and constructed to resist uplift resulting from <br />the full live load specified in Table R301.5 acting on the cantilevered portion of the <br />exterior balcony. <br />20.10.120 CRC Section R506.2.4 amended — Reinforcement support. <br />Section R506.2.4 is amended to read as follows: <br />R506.2.4 Reinforcement support. Where provided in slabs on ground, reinforcement <br />shall be supported to remain in place from the center to upper one third of the slab for <br />the duration of the concrete placement. As a minimum, and in all cases where a slab is <br />to be placed inside of a building, the slab shall be reinforced with not less than six <br />inches by six inches ten gauge welded wire mesh, or an approved alternate. <br />In all slabs under habitable spaces, a minimum of 4 inches (102 mm) of crushed rock <br />capillary water barrier shall be provided under a minimum 10 mil vapor retarder. The <br />vapor barrier shall be protected by a minimum of 2 inches (51 mm) of sand or <br />equivalent protection. <br />20.10.130 CRC Table R602.10.3(4) amended — Bracing Requirements based on <br />Seismic Design Category. <br />
The URL can be used to link to this page
Your browser does not support the video tag.