20.24.270 CFC Section 3704.1.8 added — Fire extinguishing systems. <br /> Section 3704.1.8 is added to read: <br /> 3704.1.8 Fire extinguishing systems. Buildings and covered exterior areas for storage <br /> and use areas of materials regulated by this Chapter shall be protected by an automatic <br /> fire sprinkler system in accordance with NFPA 13. The design of the sprinkler system <br /> for any room or area where highly toxic, toxic and moderately toxic gases are stored, <br /> handled or used shall be in accordance with Section 2704.5. <br /> 20.24.480 CFC Section 3704.1.9 added — Local gas shut off. <br /> Section 3704.1.9 is added to read: <br /> 3704.1.9 Local gas shut off. Manual activation controls shall be provided at locations <br /> near the point of use and near the source, as approved by the fire code official. The fire <br /> code official may require additional controls at other places, including, but not limited to, <br /> the entry to the building, storage or use areas, and emergency control stations. Manual <br /> activated shut -off valves shall be of a fail- safe -to -close design. <br /> 20.24.490 CFC Section 3704.1.10 added — Exhaust ventilation monitoring. <br /> Section 3704.1.10 is added to read: <br /> 3704.1.10 Exhaust ventilation monitoring. For gases exceeding threshold quantities, <br /> a continuous monitoring system utilizing a low switch shall be provided to assure that <br /> the required exhaust ventilation rate is maintained. The monitoring system shall initiate <br /> a local alarm. The alarm shall be both visual and audible and shall be designed to <br /> provide warning both inside and outside of the interior storage, use, or handling area. <br /> 20.24.500 CFC Section 3704.1.11 added — Emergency response plan. <br /> Section 3704.1.11 is added to read: <br /> 3704.1.11 Emergency response plan. If the preparation of an emergency response <br /> plan for the facility is not required by any other law, responsible persons shall prepare, <br /> or cause to be prepared, and filed with the fire code official, a written emergency <br /> response plan. If the preparation of an emergency response plan is required by other <br /> law, a responsible person shall file a copy of the plan with the Fire Chief. <br /> 20.24.510 CFC Section 3704.1.12 added — Emergency response liaisons. <br /> Section 3704.1.12 is added to read: <br /> 69 <br />